Transmitter Cond/Res 2-Channel M300 46
© 05/07 Mettler-Toledo AG, CH-8606 Greifensee, Switzerland Transmitter Cond/Res 2-Channel M300
Printed in Switzerland 52 121 318
10.4.1 PID Assignment & Tuning
Assign the measurement, a, b, c, or d to be controlled after “PID on_”. Set the Gain (unitless),
Integral or Reset time Tr (minutes) and Rate or Derivative time Td (minutes) needed for control.
Press [ENTER]. Gain, Reset and Rate are later adjusted by trial and error based on process
response.
10.4.2 Setpoint & Deadband
Enter the desired setpoint value and the deadband around the setpoint, where no proportional
control action will take place. Be sure to include the units multiplier µ or m. Press [ENTER].
10.4.3 Proportional Limits
Enter the low and high proportional limits – the range over which control action is required.
Be sure to include the units multiplier µ or m. Press [ENTER].
10.4.4 Corner Points
Enter the low and high corner points in conductivity units and the respective output values
from –1 to +1, shown in the figure as –100 to +100%.Press [ENTER].
10.5 PID Operation
(PATH: Menu/PID Setup/PID Display Setup)
This screen enables display of PID control status in the normal measurement mode. When PID
Display is selected, the status (Man or Auto) and control output (%) will be displayed on the
bottom line. In addition, for the display to be enabled, a measurement must be assigned under
Tune Parameters and a relay or analog output must be assigned under Mode.
In Manual, the control output may be adjusted with the up and down arrow keys. (The “Info” key
function is not available in Manual.)